Measure downflow velocity using a thermal anemometer
Match the initial set points of the cabinet ± 5 feet per minute (2.5 cm/s)
Inflow Velocity Test
Several methods and location possible for this test
Flow hood (DIM method)
Modified sash opening (see manufacturers label)
Hot wire over the exhaust HEPA filter
Match the initial set points of the cabinet ± 5 feet per minute (2.5 cm/s)
Sash/Window Seal Test
No refluxing to the outside of the window wiper gasket and side seals
Viewscreen Retention Test
Airflow along the entire perimeter of the work access opening is inward
Work Opening Edge Retention Test
Ambient air does not pass on or over the work surface
Downflow Smoke Test
Airflow within the work area is downward with no dead spots for refluxing
HEPA Filter Leak Test
Determine integrity of HEPA filter
Introduce an aerosol challenge to the cabinet
Aerosol penetration through the filter not to exceed 0.01% of the upstream concentration
Cabinet Integrity Test
To pressurize all exterior surfaces from within to assure that the plenums, welds, gaskets or seals, do not leak to the room.
Acceptance
Holds pressure within 10% for 30 minutes
No bubbles
When is integrity testing performed
Installing new units
Sealing panels are removed for maintenance
Cabinets are relocated
Annually for A1 cabinets
Site Installation Assessment Test
This is a new test for the 2001 standard. The purpose is to verify that the hood is integrated properly in the facility. The following items are compared to the manufacturer/s specifications and NSF standards.